Voltage drop
Voltage drop, the smallest conductor for a run, or the longest run for a conductor — copper or aluminium, single-phase, three-phase or DC, in PVC, aluminium or steel conduit, with paralleled sets. Worked from NEC Chapter 9 Tables 8 and 9 at your power factor, every step shown.
Calculate
How it works
For AC, Chapter 9 Table 9 gives each conductor's resistance R and reactance X per 1000 ft; its Note 2 turns them into an effective impedance at your power factor, Ze = R × PF + X × sin(arccos PF). The drop is 2 × I × Ze × L for single-phase and √3 × I × Ze × L line to line for three-phase. DC uses Table 8's resistance.
The smallest-conductor answer is the larger of the size that meets the drop and the size whose Table 310.16 ampacity carries the current at the 110.14(C) termination column — so it never suggests a wire too small to carry the load.
What it will not tell you
120/208 V 3-wire is computed as circuit analysis on Table 9's R and X: the neutral carries the line-to-neutral current, and the drop is taken on the worse phase. Unbalanced 120 V loads on the two phases are not modelled.
Resistance is Table 8 / Table 9's, at 75 °C, unless a conductor temperature is entered: then it is corrected by Table 8 Note 2. A conductor running cooler drops less.
Table 9 is three single conductors in one conduit at 60 Hz. Cable assemblies, cable tray and direct burial are close but not the table.
The minimum-size mode checks ampacity at 30 °C with three or fewer current-carrying conductors. For derating, burial and the rest of a feeder, use the NEC feeder sizing calculator.
The 3 % is an informational note, not a requirement. A larger drop is reported, never called a violation.
No report, PDF or saved project — the answer is the whole of it.